Multi-hazard screening · Piedmont
How much do energy-site rankings depend on the scoring rule?
Across five screening scenarios, 145 of 176 mapped substations and transformers had a rank range of at least 18 places.
My contribution
I built the harmonized 250 m predictor grid, the buffered model evaluation and the comparison of weighting and aggregation rules for the mapped sample.
Rank changes relative to equal weights
| Scenario | Largest change | Mean change |
|---|---|---|
| Equal weights | 0 | 0 |
| Flood focus | 65 | 13.25 |
| Landslide focus | 49 | 9.46 |
| Wildfire focus | 55 | 14.03 |
| Maximum score | 155 | 31.16 |
Rank differences refer to 176 already mapped features, with ties retained. The range across all five scenarios exceeded 10% of the sample for 145 features.
Map inputs include ISPRA, EFFIS, Copernicus, ISTAT and OpenStreetMap contributors. © OpenStreetMap.
What the project delivered
- The analysis compares landslide inventory, P2 flood zones and burned perimeters. These source labels represent different concepts.
- Landslide holdout AUC fell from 0.940 to 0.915 when the exclusion buffer increased from 5 km to 20 km on the same held-out sample.
- The scores are relative indicators. The case does not establish event probabilities, prospective failure or approved sites.
Tools and methods
- Python
- Rasterio
- QGIS
- Spatial cross-validation